Estimating Air Leakage
The amount of expected leakage can be calculated from the following equations:
Lv = 4005 x (Rp)1/2
Where,
* Lv = Leakage Velocity in feet per minute * Rp = Room Pressure in in-WG
L= 4005 x A x (Rp)1/2
Where,
* L = Air Leakage in Cubic Feet per Minute * Rp = Room Pressure in in-WG * A = Opening Area
|